Tender text – Grid and system protection ======================================== Bill of quantities item (GAEB-like, for import into tendering software) Source: https://celsa-messgeraete.de/en/planer – neutral, without manufacturer or type. Item no. 01.0010 Short text: Grid and system protection Long text: Grid and system protection relay (interface protection) monitoring voltage, frequency, ROCOF/vector shift and phase sequence, with potential-free changeover relays to control the coupling switch. For generating plants and storage (PV, CHP, storage, wind, hydro). - Grid code / requirement of the network operator: ______________ - Measuring voltage: up to 3 × 400/230 V AC - Auxiliary supply: 24 V DC or 110–230 V AC - Outputs: 3 changeover contacts (potential-free) - Digital inputs for feedback signals and remote shutdown - Interface: ______________ (Modbus RTU optional) - Event memory: 64 entries - Mounting: DIN rail, width 107 mm Functionally safe through internally redundant design, menu-guided operation, integrated test function. To be supplied, installed ready for operation and parameterised as specified by the network operator. Make offered: ______________ Type: ______________ (to be filled in by the bidder) Quantity: ______ pcs Unit price: ______________ € Total: ______________ € ----------------------------------------------------------------------------------------------------