Inicio Sobre nosotros Noticias Contacto Servicio Productos Descargas 🇩🇪 Deutsch 🇬🇧 English 🇪🇸 Español

ECM6-E MID

Solicitar ahora
Data sheet Instruction manual STEP-Datei
CELSA ECM6-E MID
Basic data
Item number
70143-1313

6A three-phase energy meter with built-in communication

  • Certified MID version
  • For Ethernet communication (Modbus TCP)
  • For 1 or 5A transducer
  • Programmable transformer ratio
  • Fully bi-directional four-quadrant measurements for all energies and powers
  • For 4-wire networks with symmetrical or asymmetrical load
  • Class B according to EN 50470-3
  • S0 output for energy pulse delivery
Technical data
Auxiliary voltage
of measuring circuit Un ± 20%
Consumption
7.5 VA, 0.5 W
Ambient conditions
Operation -25 - 55 °C
Storage -25 - 75 °C
Humidity 0 - 80 RH
Montage
DIN-Schienen Montage
Electrical connection
Display
Type
LCD
Number of digits
8
IP protection class
IP51
Connections
IP protection class
IP20
Measurement inputs conductor cross-section
1.5-6 mm²
Tariff outputs conductor cross-section
0.14-2.5 mm²
Tariff input
Tariff input
No
Metrological LED
Pulse valence
10000 imp./kWh
Pulse duration
10 ± 2 ms
Communication
Normative standards
IEEE802.3
Interfaces
Ethernet (10/100 Base T)
Protocols
Modbus TCP/IP, HTTP, NTP, DHCP
speed
10/100 Mbps
Webserver
8MB Data storage
Measurement
Active energy accuracy
Class B according to EN 50470-3
Reactive energy accuracy
Class 2 according to IEC/EN 62053-23
Starting current
2 mA
Minimum current
10 mA
Transition current
50 mA
Rated current
0 - 6 A
Nominal current
1 A
- burden
< 0.04 VA
Frequency
50 - 60 Hz
S0 output
Number of S0 outputs
1
Maximum current
27
Maximum voltage
27 DC
Pulse output
1000 Imp/kWh
> CT ratio 1-4
200 Imp/kWh
> CT ratio 5-24
40 Imp/kWh
> CT ratio 25-124
8 Imp/kWh
> CT ratio 125-624
1 Imp/kWh
> CT ratio 625-3124
0,1 Imp/kWh
> CT ratio 3125-10000
Counter constant
Standard
Pulse duration on
50 ± 2 ms
Pulse duration off
30 ± 2 ms