ECM6-E MID

| Basic data | |
|---|---|
Item number | 70143-1313 |
6A three-phase energy meter with built-in communication
- Certified MID version
- For Ethernet communication (Modbus TCP)
- For 1 or 5A transducer
- Programmable transformer ratio
- Fully bi-directional four-quadrant measurements for all energies and powers
- For 4-wire networks with symmetrical or asymmetrical load
- Class B according to EN 50470-3
- S0 output for energy pulse delivery
| Technical data | |
|---|---|
Auxiliary voltage | of measuring circuit Un ± 20% |
Consumption | 7.5 VA, 0.5 W |
Ambient conditions | Operation -25 - 55 °C Storage -25 - 75 °C Humidity 0 - 80 RH |
Montage | DIN-Schienen Montage |
Electrical connection | |
Display | |
Type | LCD |
Number of digits | 8 |
IP protection class | IP51 |
Connections | |
IP protection class | IP20 |
Measurement inputs conductor cross-section | 1.5-6 mm² |
Tariff outputs conductor cross-section | 0.14-2.5 mm² |
Tariff input | |
Tariff input | No |
Metrological LED | |
Pulse valence | 10000 imp./kWh |
Pulse duration | 10 ± 2 ms |
| Communication | |
|---|---|
Normative standards | IEEE802.3 |
Interfaces | Ethernet (10/100 Base T) |
Protocols | Modbus TCP/IP, HTTP, NTP, DHCP |
speed | 10/100 Mbps |
Webserver 8MB Data storage | |
| Measurement | |
|---|---|
Active energy accuracy | Class B according to EN 50470-3 |
Reactive energy accuracy | Class 2 according to IEC/EN 62053-23 |
Starting current | 2 mA |
Minimum current | 10 mA |
Transition current | 50 mA |
Rated current | 0 - 6 A |
Nominal current | 1 A |
- burden | < 0.04 VA |
Frequency | 50 - 60 Hz |
| S0 output | |
|---|---|
Number of S0 outputs | 1 |
Maximum current | 27 |
Maximum voltage | 27 DC |
Pulse output | 1000 Imp/kWh > CT ratio 1-4 200 Imp/kWh > CT ratio 5-24 40 Imp/kWh > CT ratio 25-124 8 Imp/kWh > CT ratio 125-624 1 Imp/kWh > CT ratio 625-3124 0,1 Imp/kWh > CT ratio 3125-10000 |
Counter constant | Standard |
Pulse duration on | 50 ± 2 ms |
Pulse duration off | 30 ± 2 ms |