Energy meters

Sale up to −60 %from €61.07 instead of €101.79incl. VATAll sale items →

MID energy meters for billing and energy management: the three-phase meters DMC100 and ECM80 for direct connection up to 100 A and 80 A, the CT-operated meters DMC6 and ECM6 for current transformers with 1 A or 5 A secondary current, and the single-phase meter WECM80. Depending on the type with Modbus RTU, Modbus TCP, M-Bus or LoRa, all with an S0 pulse output. Below the list: selection guide and FAQ.

Sub-groups

Products

Which energy meter fits?

SeriesConnectionNetworkRated currentClassInterfaces
DMC100directthree-phase 3×230/400 Vup to 100 AB (MID B+D)Modbus RTU, M-Bus, TCP/IP, LoRa; S0
DMC6CT 1 A / 5 Athree-phase 3×230/400 VCT ratio configurableB (MID B+D)Modbus RTU, M-Bus, TCP/IP, LoRa; S0
ECM80directthree-phase, 3/4-wireup to 80 AB (MID) or 1 (without MID)Modbus RTU, M-Bus, Modbus TCP; S0
ECM6CT 1 A / 5 Athree-phase, 3/4-wireCT ratio programmableB (MID)Modbus RTU, M-Bus, Modbus TCP; S0
WECM80directsingle-phaseup to 80 AB (MID) or 1 (without MID)Modbus RTU, M-Bus, Modbus TCP; S0
WECM40directsingle-phaseup to 40 AB (MID)Modbus RTU; S0

The filters above the list narrow down connection type, interface and MID; datasheet and manual can be downloaded on every product page.

Direct connection or CT-operated meter?

With a direct-connected energy meter the load current flows through the meter – up to 100 A with the DMC100, up to 80 A with ECM80 and WECM80. That is the simple solution for sub-distributions, cost centres and individual loads. Above that, a CT-operated meter measures via current transformers: DMC6 and ECM6 take 1 A or 5 A secondary current, the CT ratio is set on the meter and the primary value is displayed. Suitable ratios are listed on current transformers for meters.

All series are bidirectional meters: they record import and export separately – ECM and WECM as four-quadrant measurement – and therefore also suit installations with feed-in, such as PV systems with grid and system protection. Single-phase loads are measured by the WECM80 with a width of 2 modules; the ECM three-phase meters need 4 modules, the DMC6 5 modules.

MID: energy meters for billing

The European Measuring Instruments Directive MID (2014/32/EU, annex MI-003) defines which active energy meters may be used for billing. The MID versions by CELSA are conformity-assessed to modules B and D and measure in class B to EN 50470-3; the suffix MID in the type (DMC100-S MID, ECM80 MID, WECM80 MID) marks them. For reactive energy, ECM and WECM meet class 2 to IEC/EN 62053-23.

If billing is done via current transformers, the whole measuring chain must be approved: CT-operated meter plus calibrated current transformers ALO-E or WALO-E. For pure energy monitoring, uncalibrated transformers and meters without MID such as ECM80 or WECM80-S are sufficient. In Germany the verification period for electronic electricity meters is 8 years (MessEV, annex 7). Background in the guide MID energy meters.

Interfaces: Modbus, M-Bus, TCP/IP, LoRa and S0

For energy management to ISO 50001, cost-centre billing and building management, the meters deliver their values via an interface: RS485 with Modbus RTU (type -S), M-Bus (type -M), Ethernet with Modbus TCP (type -E) or LoRa radio (DMC-LI with internal, DMC-LE additionally with external antenna). For Loxone, a driver for the Ethernet versions DMC100-E and DMC6-E is available in the Loxone Library.

All meters also have an S0 pulse output; on the DMC100 the pulse rate is set by key (1 to 10,000 pulses per kWh). Available values: active and reactive energy per direction, active, reactive and apparent power, current and frequency, on the DMC also the number of voltage failures.

Frequently asked questions

What is an MID meter?

An energy meter that is conformity-assessed under the European Measuring Instruments Directive MID (2014/32/EU) and may therefore be used for billing electricity. The CELSA meters are assessed to modules B+D and measure in class B to EN 50470-3.

Which energy meter fits current transformers?

A CT-operated meter with an input for 1 A or 5 A secondary current, such as DMC6 MID or ECM6 MID. The ratio of the current transformer, for example 400/5 A, is set on the meter. For billing, the current transformers must be calibrated as well (ALO-E, WALO-E).

Are there MID meters with Modbus?

Yes: DMC100-S MID, DMC6-S MID, ECM80-S MID, ECM6-S MID and WECM80-S MID with RS485 Modbus RTU; DMC100-E, DMC6-E, ECM80-E, ECM6-E and WECM80-E MID with Modbus TCP over Ethernet.

Direct connection or CT-operated – which do I need?

Up to 100 A (DMC100) or 80 A (ECM80, WECM80) load current a direct-connected meter is sufficient. Above that – or if the conductor is not to be routed through the meter – a CT-operated meter measures via current transformers.

Do the meters also record exported energy?

Yes, all series are bidirectional and count import and export separately; ECM and WECM measure in four quadrants.

Which energy meter for a single-phase measurement?

The WECM80 up to 80 A with a width of 2 modules – as WECM80 MID for billing, as WECM80-S, -M or -E without MID for monitoring.

How long is the verification of an MID meter valid?

In Germany 8 years under annex 7 of the Measuring and Verification Ordinance (MessEV); after that the meter is re-verified or replaced.

What is the S0 output for?

The S0 pulse output emits one pulse per recorded amount of energy, which counters, data loggers and energy management systems without a bus connection evaluate; on the DMC100 the pulse rate is adjustable.