Current transformer calculation: VA calculator
Calculate the required VA burden rating for your current transformer
Correct dimensioning of a current transformer's burden is critical for measurement accuracy. An insufficient VA rating leads to saturation and inaccurate measurements. This calculator considers cable losses, connected instrument consumption and contact resistance to recommend the optimal VA rating.
Input values
Typical values for the measuring circuit – the exact figure is in your instrument data sheet.
Result
- Cable burden
- 1.78 VA
- Instrument burden
- 0.50 VA
- Contact resistance
- 0.10 VA
- Total burden
- 2.38 VA
- Recommended VA rating
- 2.5 VA
Burden distribution
VA rating utilization
Calculation formula
R = (2 × L × 0,0178) / APKabel = Is² × RPges = PKabel + PGeräte + 0,1 VAWhere ρ = 0.0178 Ω·mm²/m is the resistivity of copper, L the one-way cable length in m and A the cable cross-section in mm². The factor 2 accounts for the forward and return conductor.
Frequently asked questions
How do I calculate the burden?
Lead loss = secondary current² × lead resistance, with R = 2 × length × 0.0178 Ω·mm²/m ÷ cross-section. Example: 5 A, 5 m, 2.5 mm² give 0.0712 Ω and 1.78 VA. Add 0.5 VA for the meter and 0.1 VA for contacts: 2.38 VA – a 2.5 VA transformer is recommended.
Why 1 A for long leads?
Lead loss grows with the square of the current. The same lead (5 m, 2.5 mm²) consumes only 0.07 VA at 1 A instead of 1.78 VA at 5 A.
Which rated outputs are available?
The calculator picks the next standard rating above the calculated burden: 1, 1.5, 2.5, 5, 10, 15 or 30 VA.