Current transformer calculation: VA calculator

Calculate the required VA burden rating for your current transformer

Correct dimensioning of a current transformer's burden is critical for measurement accuracy. An insufficient VA rating leads to saturation and inaccurate measurements. This calculator considers cable losses, connected instrument consumption and contact resistance to recommend the optimal VA rating.

Input values

Typical values for the measuring circuit – the exact figure is in your instrument data sheet.

Result

Cable burden
1.78 VA
Instrument burden
0.50 VA
Contact resistance
0.10 VA
Total burden
2.38 VA
Recommended VA rating
2.5 VA

Burden distribution

CableInstrumentsContact

VA rating utilization

95 %

Calculation formula

Cable resistance:
R = (2 × L × 0,0178) / A
Cable losses:
PKabel = Is² × R
Total burden:
Pges = PKabel + PGeräte + 0,1 VA

Where ρ = 0.0178 Ω·mm²/m is the resistivity of copper, L the one-way cable length in m and A the cable cross-section in mm². The factor 2 accounts for the forward and return conductor.

Calculating the burden of a current transformer: cable loss 3.56 VA (5 A, 10 m, 2.5 mm²) plus instrument 0.5 VA plus contacts 0.1 VA gives 4.16 VA, a 5 VA rating is chosen
The burden is the sum of the cable loss (outgoing and return lead), the instrument consumption and 0.1 VA for terminals and contacts. It must stay below the rated burden of the transformer.

Frequently asked questions

How do I calculate the burden?

Lead loss = secondary current² × lead resistance, with R = 2 × length × 0.0178 Ω·mm²/m ÷ cross-section. Example: 5 A, 5 m, 2.5 mm² give 0.0712 Ω and 1.78 VA. Add 0.5 VA for the meter and 0.1 VA for contacts: 2.38 VA – a 2.5 VA transformer is recommended.

Why 1 A for long leads?

Lead loss grows with the square of the current. The same lead (5 m, 2.5 mm²) consumes only 0.07 VA at 1 A instead of 1.78 VA at 5 A.

Which rated outputs are available?

The calculator picks the next standard rating above the calculated burden: 1, 1.5, 2.5, 5, 10, 15 or 30 VA.