Knowledge base
Fundamentals, selection guides and calculators for current measurement
28 articles
VA power calculator
Determines the required VA rating from cable length, cross-section and the burden of the connected instruments.
Current transformers – function, types, classes, burden, connection
The main page: how a current transformer works, types, ratio, accuracy classes, burden, connection and selection help – with all ratios.
Transformer finder
Step by step to the right current transformer: what for, how mounted, which current – you end up with real article numbers from our range.
Cable cross-section for the burden
Which cross-section does the measuring cable need so that the rated burden is sufficient? The counterpart to the VA calculator.
Cable losses and cable length in the secondary circuit
How many VA does the measuring cable between current transformer and instrument consume? Calculates cable burden, total burden against the rated output and the maximum cable length – with a recommendation on 1 A or a larger cross-section.
Which accuracy class do I need?
Permissible current error and phase displacement of the classes to IEC 61869-2 – including partial load, where the differences are largest.
Check short-circuit withstand
Will the transformer withstand the fault current of your installation? Converts the rated short-time current to your clearing time.
Choosing a current transformer in 4 steps
Four parameters decide which current transformer fits: the primary current with the secondary output (the ratio), the type for your conductor, the accuracy class and the rated output in VA for the burden. This page walks through the choice in exactly this order.
Plug-on current transformers: design, mounting and selection
A plug-on current transformer (also window-type or bar-type CT) has no primary winding of its own: the primary conductor – busbar or cable – passes through the window and forms a single-turn primary. On the secondary side the transformer delivers 1 A, 5 A or 333 mV to meter, instrument or transducer. Because the conductor must pass through the closed window, the plug-on CT is the design for new installations and switchgear; for retrofitting without disconnection there are split-core CTs.
Analogue panel meters: moving-iron, moving-coil or bimetal?
Analogue meters show current and voltage with a pointer on a scale – without auxiliary supply, without configuration and still readable during disturbances. In panels, cabinets and distribution boards they therefore remain the standard indication for a glance at the load. Which instrument fits is decided by the movement: it determines whether AC or DC quantities are measured and what the pointer shows.
Shunt resistor: measuring DC current with 60 mV to 300 mV
A shunt resistor is a low-ohm precision resistor in the DC circuit. When rated current flows through it, a small, precisely defined voltage drops across it – at CELSA 60 mV, 80 mV, 100 mV, 150 mV or 300 mV. A moving-coil instrument or a digital meter measures this voltage and displays it as current. Current transformers only work with AC; for DC the shunt is the classic way.
Hour meters: how they count, how they are connected, which one fits
An hour meter counts the time during which voltage is present at its terminals. It is connected in parallel with the motor, pump, compressor or the contactor that switches the plant on – when the plant runs, the meter runs. This yields the operating hours for maintenance intervals, oil changes, warranty and rental billing.
Measuring DC current: why no current transformer, and what instead
Anyone searching for “DC current transformer” or “DC CT 4–20 mA” runs into a physical problem: a current transformer is a transformer. It only transfers AC quantities, because only a changing primary current induces a voltage in the core. With DC the core saturates and nothing flows on the secondary side. CELSA therefore manufactures current transformers exclusively for AC – and for DC a measuring chain of shunt and display.
Wound current transformers for flexible primary currents
Wound current transformers are ideal when flexible primary design and custom ratios are required.
Summation current transformers: several feeders on one meter
A summation current transformer adds the secondary currents of several main current transformers (x/5 A or x/1 A) into a single output signal of 5 A or 1 A. One measuring device or energy meter then records the total current and energy of several feeders, incomers or transformers.
4–20 mA transducers: current transformer with transducer
A current transformer delivers 1 A, 5 A or 333 mV – but PLCs and control systems usually expect a standard signal such as 4–20 mA. The transducer sits in between: it is connected to the secondary side of the CT and converts the measured quantity into an impressed DC current that stays stable over long cables.
MID energy meters: what the directive means for meters
MID stands for the European Measuring Instruments Directive 2014/32/EU. Its annex MI-003 defines the requirements an active energy meter must meet so that it may be used for billing without national initial verification: the manufacturer has the type examined (module B) and secures production through a supervised quality system (module D). An MID meter carries the CE marking with the metrology mark; the CELSA MID meters are assessed to modules B+D and measure in class B to EN 50470-3.
Digital panel meters for switchboards and distribution cabinets
Digital panel meters provide readable values for current, voltage, power and process variables.
Grid protection relays: grid and system protection explained
A grid protection relay – in German grid operators’ terms the NA-Schutz, grid and system protection – sits at the point of connection of a generating plant. It measures the three phase voltages against N, evaluates voltage, frequency, rate of change of frequency (ROCOF) or vector shift and the phase sequence, and opens the connection to the grid via the coupling switch as soon as a value leaves the set limits. This prevents a PV system, CHP unit or storage from feeding into a disturbed or de-energised grid – protecting the grid, personnel and the plant.
Rogowski coil: function, advantages and use of flexible current measurement
A Rogowski coil is a flexible air-core coil without an iron core that is placed around the conductor and closed with a clasp. The alternating current in the conductor induces a voltage in the coil proportional to the rate of change of the current. A downstream integrator – in an instrument or energy meter with Rogowski input – turns it into a signal proportional to the current.
Protection current transformers 5P and 10P: protection classes, accuracy limit factor and selection
Whereas metering transformers should saturate as quickly as possible above their operating current range (expressed by the instrument security factor FS), protection current transformers are required to saturate as far outside this range as possible. This way even a high fault current reaches the protection relay undistorted and the circuit breaker trips correctly.
Cable conversion current transformers for retrofit installation
Cable conversion current transformers are the ideal solution when CTs need to be installed retrospectively without interrupting the primary circuit. The compact design and easy mounting with UV-resistant cable ties make them highly practical.
Connecting a current transformer: wiring diagram and steps
A current transformer has two sides to connect: on the primary side it sits on the conductor, on the secondary side two leads run from S1 and S2 to the meter. Four rules decide whether the measurement is correct and safe – mounting direction, secondary wiring, earthing at one point and short-circuiting before the secondary circuit is ever opened.
Current transformer accuracy classes: 0.2, 0.5, 1 and 0.2S, 0.5S explained
The accuracy class of a current transformer states the permissible ratio error in percent at rated current. A class 0.5 transformer may deviate from the ideal ratio by at most ±0.5 % at 100 % and 120 % of rated primary current and shift the current by at most ±30 minutes of arc. The basis is the standard IEC 61869-2.
Calculating the burden: how to size the VA rating of a current transformer
The burden is the load a current transformer has to drive in the secondary circuit – stated as apparent power in VA at rated secondary current. It consists of the consumption of the connected meters, instruments or relays, the resistance of the measuring lead (outgoing and return conductor) and the contact resistances at terminals.
Calibration and MID: calibrated current transformers and MID meters for billing
Anyone billing electrical energy to third parties – tenants, sub-tenants, charging points or other companies – needs approved measuring instruments. In CT-operated metering these are two parts: the energy meter and the current transformers in front of it. Different rules apply to each.
Plug-on, cable split-core or busbar split-core current transformer: the types compared
The three common types differ mainly in one question: does the primary conductor have to be opened for installation? With the plug-on current transformer it does – the conductor passes through the closed window. Cable and busbar split-core transformers have a divisible core and are placed around the conductor; the circuit stays closed.
Calculating a current transformer: ratio, CT factor and sizing
The ratio of a current transformer is the quotient of rated primary and secondary current: Kn = Ipn / Isn. A 400/5 A transformer has a ratio of 80, a 400/1 A transformer 400. Everything else follows: the secondary current is the primary current divided by Kn, the primary current is the measured secondary current times Kn. With 320 A through a 400/5 A CT, it delivers 320 / 80 = 4 A to the instrument.