Plug-on current transformers: design, mounting and selection

A plug-on current transformer (also window-type or bar-type CT) has no primary winding of its own: the primary conductor – busbar or cable – passes through the window and forms a single-turn primary. On the secondary side the transformer delivers 1 A, 5 A or 333 mV to meter, instrument or transducer. Because the conductor must pass through the closed window, the plug-on CT is the design for new installations and switchgear; for retrofitting without disconnection there are split-core CTs.

The CELSA ALO series covers 50 A to 6000 A in 15 housing sizes, from the ALO R21 (round conductors up to ⌀ 20 mm) via ALO 3015, 4012 and 5012 for small distribution boards to ALO 16050 and 20060 for busbar packs up to 6000 A (round conductors up to ⌀ 95 mm). Accuracy classes are 0.5 and 1, small ratios of the ALO 3015 and 4012 also class 3; rated outputs go up to 30 VA. For primary currents from 1 A to 40 A there is the wound primary CT WALO, for billing the calibrated versions ALO-E and WALO-E.

All ALO have a rotatable, sealable secondary terminal cover that short-circuits the transformer when the cover is open – no CT test terminal needed. They can be mounted on the base or the side; mounting material for busbar and cable is included. According to the datasheet they are currently the most compact design on the market and therefore intended for the control cabinet.

Three plug-on current transformers 400/5 A on busbars L1, L2 and L3 of a main distribution, secondary wiring with 5 A to the meter
Plug-on current transformers in the main distribution: one transformer per phase sits on the busbar and supplies the meter with a small current at a fixed ratio – 5 A for 400/5 A.
  1. Step 1: Choose the ratio by operating current

    The rated primary current sits just above the highest operating current of the feeder, i.e. 100/5 A for a feeder up to 100 A. Chosen too large, the transformer measures inaccurately at partial load; class 0.5 only applies from 5 % of rated current. 5 A is the standard secondary; 1 A keeps losses on long leads small, 333 mV feeds energy monitoring devices almost without current.

  2. Step 2: Choose the window by busbar or cable

    The window must take the conductor: ALO R21 for round conductors up to ⌀ 20 mm, ALO 3015 up to ⌀ 28 mm, ALO 4012 up to ⌀ 33 mm, ALO 5012 up to ⌀ 42 mm, ALO 6015.8 and 6040 up to ⌀ 52 and 56 mm, ALO 8030 up to ⌀ 64 mm, ALO 10030 to 12070 up to ⌀ 75 to 85 mm and ALO 16050 up to ⌀ 95 mm. Busbar dimensions of each type are in the datasheet; the larger housings also take several bars side by side.

  3. Step 3: Check class and burden

    Class 1 is sufficient for indication and monitoring, class 0.5 for energy monitoring and sub-meters, billing third parties requires a calibrated ALO-E (class 0.2S to 0.5). The rated output in VA must cover the consumption of the connected devices plus the losses of the measuring lead – the VA calculator works it out.

  4. Step 4: Mount and connect

    Fix the transformer to busbar or cable with the supplied material, observe the direction of energy flow K → L (P1 → P2), connect the secondary leads to S1 (k) and S2 (l), close the terminal cover and seal it if required. A current transformer must never be operated with an open secondary – the ALO terminal cover short-circuits it automatically when opened.

Calculators and related pages

Typical Applications

Recommended Products

FAQ

What is the difference between a plug-on and a window-type current transformer?

None – both describe the same design: the primary conductor passes through the window, the transformer sits on busbar or cable. CELSA calls the ALO series plug-on current transformers.

Does the circuit have to be interrupted for installation?

Yes. Busbar or cable must pass through the closed window, which is why plug-on CTs are mainly used in new installations. For retrofitting under operation there are split-core, cable and busbar split-core CTs.

Which currents do plug-on CTs cover?

The ALO series 50 A to 6000 A primary, secondary 1 A, 5 A or 333 mV. Below that, from 1 A to 40 A, the wound primary CT WALO takes over.

Are there plug-on CTs for billing?

Yes, the calibrated ALO-E (50 A to 5000 A, classes 0.2S, 0.2, 0.5S, 0.5) and WALO-E (1 A to 40 A), conformity-assessed with a PTB type-examination certificate under the German MessEG/MessEV.

What is a protection plug-on CT?

A plug-on CT in protection class 5P or 10P that transfers even high overcurrents faithfully so protection relays trip reliably. At CELSA these are the protection CTs IB, IBG, IBR, IER, IRM, IRP and ICM for 75 A to 4000 A.

Why must a current transformer never be left open on the secondary side?

With an open secondary the terminal voltage rises to dangerous values and the core is overloaded. That is why secondary terminals are short-circuited during work; the ALO terminal cover does this itself when opened.