Plug-on, cable split-core or busbar split-core current transformer: the types compared

The three common types differ mainly in one question: does the primary conductor have to be opened for installation? With the plug-on current transformer it does – the conductor passes through the closed window. Cable and busbar split-core transformers have a divisible core and are placed around the conductor; the circuit stays closed.

The closed core of the plug-on transformer provides the highest rated outputs in a small housing and is the only one of the three types also available calibrated (ALO-E). Cable split-core transformers are very compact and deliver little power – suited to digital instruments with short leads. Busbar split-core transformers open at the push of a button, click audibly into place and cover busbars up to 3000 A.

For both cable and busbar there is the KALO split-core transformer. All CELSA current transformers comply with DIN EN 61869.

Three types compared: plug-on current transformer 1 to 6000 A and 1 to 30 VA, circuit must be opened; cable split-core 60 to 1000 A and 0.2 to 1 VA and busbar split-core 60 to 3000 A and 1.25 to 60 VA without shutdown
Plug-on, cable and busbar split-core current transformers: the plug-on type has a closed core and delivers the most power, the two split-core types are placed around cable or busbar without shutdown.

The three types compared

Plug-on current transformerCable split-core transformerBusbar split-core transformer
Installationconductor through the window, circuit must be openedplace around the cable, secure with UV-resistant cable tieopen at the push of a button, place around the busbar, fix with clamping screws
Rated primary current1 A to 6000 A (small currents as wound CT)60 A to 1000 A60 A to 3000 A
Secondary1 A, 5 A, 333 mV1 A, 5 A, 333 mV1 A, 5 A
Accuracy classes0.5; 1; 3 – calibrated 0.2S; 0.2; 0.5S; 0.50.5; 1; 30.5; 1; 3
Rated output1 VA to 30 VA0.2 VA to 1 VA1.25 VA to 60 VA
Secondary connectionscrew terminals with rotatable, sealable coverfixed, colour-coded leadsscrew terminals
For billing (calibrated)yes, as ALO-E / WALO-Enono
Typical usenew installations, control cabinet, main distributionretrofit, energy monitoring, digital instrumentsretrofit on busbars, high currents
CELSA seriesALO, WALO, ALO-ETQ, TCIAP, IAM, IAG

Ranges across all versions of each type in the CELSA range; the product list shows which combination of current, class and output exists for each window size.

Calculators and related pages

Recommended Products

FAQ

What is the difference between plug-on and cable split-core transformers?

The plug-on transformer has a closed core; the conductor passes through the window, so the circuit must be opened. The cable split-core transformer has a divisible core and is placed around the existing cable – without shutdown. In return it delivers much less power (0.2 VA to 1 VA).

Do I have to shut down the installation for a plug-on transformer?

Yes, the primary conductor has to pass through the closed window. That is why plug-on transformers are mostly used in new installations. For retrofitting during operation there are cable and busbar split-core transformers.

When do I use a busbar split-core transformer?

When retrofitting an existing busbar that needs more power or higher currents than a cable split-core transformer offers: busbar split-core transformers are available from 60 A to 3000 A and with up to 60 VA.

Why do cable split-core transformers have so few VA?

The small divisible core only delivers a low rated output of 0.2 VA to 1 VA. That is enough for digital instruments and energy meters with low consumption and short leads. The cable loss calculator shows how long the lead may be.

Can I use split-core transformers for billing?

Not in the CELSA range: the calibrated types are the ALO-E plug-on and WALO-E wound current transformers. Cable and busbar split-core transformers suit operational metering and energy monitoring.

What does 333 mV secondary output mean?

Instead of a current, the transformer delivers a voltage of 333 mV at rated current. It is intended for energy meters and monitoring systems with voltage input and cannot be combined with devices for 1 A or 5 A.

Are split-core transformers less accurate?

CELSA also offers cable and busbar split-core transformers in class 0.5. What matters is that the burden suits the small rated output – otherwise the class is not met.