Cable split-core current transformers
Cable split-core current transformers are opened, placed around the existing cable and secured with UV-resistant cable ties – the circuit stays in operation. The TQ and TC series cover 60 A to 1000 A, secondary 1 A, 5 A or 333 mV, for cables up to 42 mm diameter. The table shows which type fits cable and ratio; every ratio of the cable split-core CTs has its own page.
Products
Which cable split-core CT fits?
| Type | Primary current | Secondary | Class | Rated output | Cable up to ⌀ |
|---|---|---|---|---|---|
| TC 18 | 60 A to 250 A | 1 A, 333 mV | 1, 3 | 0.2 VA | 18 mm |
| TQ 18-B | 100 A to 250 A | 1 A, 5 A | 0.5, 1 | 0.2 to 1 VA | 18 mm |
| TQ 27 | 150 A to 500 A | 1 A, 5 A, 333 mV | 0.5, 1 | 0.2 to 1 VA | 28 mm |
| TQ 42 | 250 A to 1000 A | 1 A, 5 A, 333 mV | 0.5, 1 | 0.5 VA | 42 mm |
| TQ 84 | 250 A to 1000 A | 1 A, 5 A | 0.5, 1 | 0.5 VA | 42 mm |
For cables and busbars alike: split-core CTs KALO 2010, 3015 and 5012 (100 A to 1000 A, round conductors ⌀ 9, 27 and 43 mm). For busbars: busbar split-core CTs IAG, IAM and IAP.
Split-core CTs for retrofits
The cable split-core CTs are very compact and fit into tight spaces. They come with colour-coded connection leads and are particularly suited to digital meters and energy monitoring – as well as normal metering. All comply with DIN EN 61869.
Rated outputs range from 0.2 VA to 1 VA – enough for energy meters and digital instruments with short leads. For longer secondary leads, check the burden with the VA calculator; the 333 mV versions (TC 18, TQ 27, TQ 42) are insensitive to lead length because they work almost without current.
Installation: open the transformer, place it around the cable, close it and fix it to the cable with the supplied UV-resistant cable ties. Observe the arrow (K → L, direction of energy flow), then connect S1/S2 to meter or instrument. The guide on connecting a current transformer shows it step by step.
Cable split-core, retrofit or clamp-on CT – the terms
Cable split-core CT, cable conversion CT and retrofit CT all describe the same design: an openable current transformer for cables. They belong to the split-core current transformers as a whole – including busbar split-core CTs and the KALO for cable and busbar.
Several cable split-core CTs can be combined by the summation current transformer SSRK into one reading, for example for several feeders on one meter.
Frequently asked questions
What is a cable split-core current transformer?
An openable current transformer placed around an existing cable without interrupting the primary circuit. It is secured with UV-resistant cable ties.
Which cable split-core CT fits my cable?
The cable diameter decides: TC 18 and TQ 18-B take cables up to 18 mm, TQ 27 up to 28 mm, TQ 42 and TQ 84 up to 42 mm. Then choose the ratio by operating current – e.g. 250/5 A for a feeder up to 250 A.
Which cable split-core CTs are available with 333 mV?
TC 18, TQ 27 and TQ 42. TQ 18-B and TQ 84 deliver 1 A or 5 A.
Which accuracy classes do cable split-core CTs have?
TQ in class 0.5 or 1, TC 18 in class 1 or 3 – the class is part of each article name.
Are cable split-core CTs calibrated?
No, they are operational metering transformers for indication, monitoring and energy monitoring. Billing third parties requires [calibrated current transformers](/produkte/geeichte-aufsteckstromwandler) ALO-E or WALO-E, for which the conductor must be free.
Cable split-core or plug-on current transformer?
Split-core for retrofitting without shutdown, plug-on for new installations where the conductor is free – they are the more economical design.