Cable split-core current transformers

Cable split-core current transformers are opened, placed around the existing cable and secured with UV-resistant cable ties – the circuit stays in operation. The TQ and TC series cover 60 A to 1000 A, secondary 1 A, 5 A or 333 mV, for cables up to 42 mm diameter. The table shows which type fits cable and ratio; every ratio of the cable split-core CTs has its own page.

Which cable split-core CT fits?

TypePrimary currentSecondaryClassRated outputCable up to ⌀
TC 1860 A to 250 A1 A, 333 mV1, 30.2 VA18 mm
TQ 18-B100 A to 250 A1 A, 5 A0.5, 10.2 to 1 VA18 mm
TQ 27150 A to 500 A1 A, 5 A, 333 mV0.5, 10.2 to 1 VA28 mm
TQ 42250 A to 1000 A1 A, 5 A, 333 mV0.5, 10.5 VA42 mm
TQ 84250 A to 1000 A1 A, 5 A0.5, 10.5 VA42 mm

For cables and busbars alike: split-core CTs KALO 2010, 3015 and 5012 (100 A to 1000 A, round conductors ⌀ 9, 27 and 43 mm). For busbars: busbar split-core CTs IAG, IAM and IAP.

Split-core CTs for retrofits

The cable split-core CTs are very compact and fit into tight spaces. They come with colour-coded connection leads and are particularly suited to digital meters and energy monitoring – as well as normal metering. All comply with DIN EN 61869.

Rated outputs range from 0.2 VA to 1 VA – enough for energy meters and digital instruments with short leads. For longer secondary leads, check the burden with the VA calculator; the 333 mV versions (TC 18, TQ 27, TQ 42) are insensitive to lead length because they work almost without current.

Installation: open the transformer, place it around the cable, close it and fix it to the cable with the supplied UV-resistant cable ties. Observe the arrow (K → L, direction of energy flow), then connect S1/S2 to meter or instrument. The guide on connecting a current transformer shows it step by step.

Cable split-core, retrofit or clamp-on CT – the terms

Cable split-core CT, cable conversion CT and retrofit CT all describe the same design: an openable current transformer for cables. They belong to the split-core current transformers as a whole – including busbar split-core CTs and the KALO for cable and busbar.

Several cable split-core CTs can be combined by the summation current transformer SSRK into one reading, for example for several feeders on one meter.

Frequently asked questions

What is a cable split-core current transformer?

An openable current transformer placed around an existing cable without interrupting the primary circuit. It is secured with UV-resistant cable ties.

Which cable split-core CT fits my cable?

The cable diameter decides: TC 18 and TQ 18-B take cables up to 18 mm, TQ 27 up to 28 mm, TQ 42 and TQ 84 up to 42 mm. Then choose the ratio by operating current – e.g. 250/5 A for a feeder up to 250 A.

Which cable split-core CTs are available with 333 mV?

TC 18, TQ 27 and TQ 42. TQ 18-B and TQ 84 deliver 1 A or 5 A.

Which accuracy classes do cable split-core CTs have?

TQ in class 0.5 or 1, TC 18 in class 1 or 3 – the class is part of each article name.

Are cable split-core CTs calibrated?

No, they are operational metering transformers for indication, monitoring and energy monitoring. Billing third parties requires [calibrated current transformers](/produkte/geeichte-aufsteckstromwandler) ALO-E or WALO-E, for which the conductor must be free.

Cable split-core or plug-on current transformer?

Split-core for retrofitting without shutdown, plug-on for new installations where the conductor is free – they are the more economical design.