Voltage transformers: instrument transformers for voltage
A voltage transformer is connected in parallel with the voltage and reproduces it as a standardised secondary value – to IEC 61869-3 usually 100 V or 110 V, divided by √3 when connected between line and earth. It is needed where the system voltage is too high to be applied directly to a meter or instrument: in medium- and high-voltage installations.
At low voltage – up to 1000 V AC – the voltage is normally measured directly. Meters, digital instruments, voltmeters and grid protection relays take the voltage straight from the mains; only the current passes through current transformers. CELSA therefore manufactures current transformers, not voltage transformers. For voltage measurement in distribution boards and switchboards the range offers digital instruments, analogue voltmeters and the grid and plant protection relay CEL-NA-S.
Instrument transformers for billing and protection
For energy measurement the accuracy class matters: CELSA manufactures measuring CTs in classes 0.5, 1 and 3 and calibrated CTs for billing in 0.2S, 0.2, 0.5S and 0.5. Which class a metering point needs is set by the grid or metering operator. Protection CTs carry protection classes from 5P5 to 10P10; they saturate deliberately late so that the relay also sees the short-circuit current correctly – the opposite of the measuring CT, which saturates early and so protects the instruments.
The classes in detail, the difference between 0.5 and 0.5S and the requirements for calibrated CTs are covered in the articles accuracy classes of current transformers, calibration and MID and protection current transformers.
Instrument transformer or transducer?
An instrument transformer is passive: it needs no auxiliary power and passes the current or voltage on reduced but in the same form – alternating current flows again on the secondary side. A transducer is an electronic device with auxiliary supply that turns the measured quantity into a standard signal such as 4–20 mA or 0–10 V for control and SCADA systems. In the measuring chain the current transformer comes before the transducer: the CT delivers 5 A or 1 A, the transducer turns it into the standard signal.
Instrument transformers for switchgear and distribution boards
In the low-voltage main distribution board and the switchboard the current transformer sits on the cable or busbar, with the meter or instrument next to it on the DIN rail. For new installations the plug-on CT is the rule, for retrofits in service the split-core CT, for several feeders on one meter the summation CT and for very high currents the Rogowski coil. The conditions of use apply to all CELSA current transformers:
Conditions of use of CELSA current transformers
| Secondary current | 5 A or 1 A |
|---|---|
| Rated frequency | 50 – 60 Hz |
| Max. permissible operating voltage | 720 V |
| Test voltage | 3 kV / 1 min |
| Insulation class | E to IEC 85 |
| Standards | IEC 61869 parts 1 + 2 / DIN EN 42600 |
Values from the technical data on the product pages. Special versions on request: any primary and secondary rated currents, operating voltage series 1 (1.2 kV), resin encapsulation.