4–20 mA transducers: current transformer with transducer
A current transformer delivers 1 A, 5 A or 333 mV – but PLCs and control systems usually expect a standard signal such as 4–20 mA. The transducer sits in between: it is connected to the secondary side of the CT and converts the measured quantity into an impressed DC current that stays stable over long cables.
The CELSA power transducers Pw-MU, Pnz-MU, Pz-MU, Pd-MU and Pdr-MU have current inputs for 1 A or 5 A and output the active power of single- and three-phase systems as 4–20 mA (with 2–10 V), 0–20 mA (with 0–10 V) or 0–10 mA. Input and output are galvanically isolated, the outputs are open- and short-circuit proof, class 0.5.
With 4–20 mA (live zero) a reading of zero corresponds to 4 mA. If the signal drops to 0 mA, the controller detects a broken wire. Live zero requires an auxiliary supply – available for 24 V DC, 230 V AC or 36–265 V AC/DC. To convert or isolate an existing standard signal, the DTVU20 isolating amplifier is the right signal converter.
Typical Applications
- Signal adaptation for PLC and control systems
- Galvanic isolation in measuring chains
- Reliable transmission over long cable distances
Recommended Products
FAQ
How do I connect a transducer to a current transformer?
The secondary terminals S1 and S2 of the CT go to the current input of the transducer (1 A or 5 A, matching the CT); the voltage is taken directly from the supply. The 4–20 mA output goes to the controller. Short-circuit the CT secondary before disconnecting it.
Are there current transformers with a 4–20 mA output?
A current transformer itself delivers 1 A, 5 A or 333 mV. The 4–20 mA signal comes from the downstream transducer or the analogue output of a digital meter.
Why 4–20 mA instead of 0–20 mA or 0–10 V?
With live zero (4 mA = zero reading) a broken wire shows as 0 mA. Current signals are also insensitive to voltage drops and interference on long cables.