Protection current transformers 5P and 10P: protection classes, accuracy limit factor and selection
Whereas metering transformers should saturate as quickly as possible above their operating current range (expressed by the instrument security factor FS), protection current transformers are required to saturate as far outside this range as possible. This way even a high fault current reaches the protection relay undistorted and the circuit breaker trips correctly.
The protection class describes this: with 5P10 the composite error is at most 5 % up to 10 times rated current. The number before the P is the permissible composite error in percent, the number after it the accuracy limit factor (ALF). At rated current class 5P allows a current error of ±1 % and a phase displacement of ±60 minutes, class 10P a current error of ±3 %.
CELSA protection current transformers are available in classes 5P5, 5P10, 10P5 and 10P10 for rated primary currents from 75 A to 4000 A, 1 A or 5 A secondary and rated outputs from 1.25 VA to 45 VA. They comply with DIN EN 61869, have sealable secondary terminal covers made of transparent polycarbonate and double secondary terminals for short-circuiting before the secondary circuit is opened.
Protection classes to IEC 61869-2
| Class | Current error at In | Phase displacement at In | Composite error up to ALF · In | Meaning |
|---|---|---|---|---|
| 5P5 | ±1 % | ±60′ | 5 % | at most 5 % composite error up to 5 times rated current |
| 5P10 | ±1 % | ±60′ | 5 % | at most 5 % composite error up to 10 times rated current |
| 10P5 | ±3 % | not specified | 10 % | at most 10 % composite error up to 5 times rated current |
| 10P10 | ±3 % | not specified | 10 % | at most 10 % composite error up to 10 times rated current |
The values apply at rated burden. All four classes are available in the CELSA range, for 75 A to 4000 A.
Calculators and related pages
Typical Applications
- Overcurrent and short-circuit protection with protection relays
- Selective system protection in low-voltage distribution
- Standard-compliant protection per DIN EN 61869
Recommended Products
FAQ
What distinguishes protection CTs from metering CTs?
Protection CTs saturate far out so that the protection signal is transmitted correctly even at short-circuit currents. Metering CTs, by contrast, deliberately saturate early (e.g. FS 5) to protect the connected instruments.
What does 5P10 mean?
Up to 10 times rated current the composite error stays below 5 %. The 5 stands for the composite error in percent, P for protection, the 10 for the accuracy limit factor ALF.
What is the difference between 5P and 10P?
5P allows 5 % composite error up to the accuracy limit current, 10P allows 10 %. At rated current a 5P transformer may have ±1 % current error and ±60′ phase displacement, a 10P transformer ±3 % with no specified phase displacement. The required class is specified by the relay manufacturer or the protection design.
How does the accuracy limit factor depend on the burden?
The ALF applies at rated burden. If the actual burden is lower, the transformer saturates only at higher currents and the effective ALF rises. If it is higher – for example due to long leads – it falls. So calculate the burden of relay and leads and choose the rated output to match.
Can I use a metering CT for protection?
No. With a metering CT of FS 5 the composite error is already at least 10 % at 5 times rated current; during a short circuit the relay then receives too small a current and may trip late or not at all.
Where are protection current transformers used?
For system protection together with circuit breakers, protection relays and other switchgear, for example for overcurrent and short-circuit protection in low-voltage distribution.