Grid protection relays: grid and system protection explained
A grid protection relay – in German grid operators’ terms the NA-Schutz, grid and system protection – sits at the point of connection of a generating plant. It measures the three phase voltages against N, evaluates voltage, frequency, rate of change of frequency (ROCOF) or vector shift and the phase sequence, and opens the connection to the grid via the coupling switch as soon as a value leaves the set limits. This prevents a PV system, CHP unit or storage from feeding into a disturbed or de-energised grid – protecting the grid, personnel and the plant.
The limit values and tripping times are defined by the VDE technical connection rules: VDE-AR-N 4105 for low voltage, 4110 for medium voltage and 4120 for high voltage. In the low-voltage grid, the protection integrated in the inverter is sufficient up to 30 kVA; above that VDE-AR-N 4105 requires a central protection with its own relay and coupling switch. The specific settings are given by the grid operator; the relay is parameterised accordingly and the settings are documented.
The CEL-NA-S by CELSA is such a relay to VDE-AR-N 4105/4110/4120: measuring input 3×400 V AC, phase-to-phase voltage 0–560 V, frequency 40–65 Hz, ROCOF 100–2,000 mHz/s, phase shift 1–15°. Three potential-free changeover relays control the coupling switch, digital inputs take its feedback and a remote shutdown, Modbus RTU is optional. The internally redundant design makes it functionally safe; it is menu-guided with an integrated test function and 64 memory locations, auxiliary supply 24 V DC or 110–230 V AC, modular installation 107 mm wide.
Calculators and related pages
Typical Applications
- Grid and plant protection in generation systems
- Monitoring voltage and frequency thresholds
- Safe disconnection in fault conditions
Recommended Products
FAQ
What is the difference between a grid protection relay and NA protection?
NA protection (grid and system protection) is the protective function at the grid connection as a whole – measurement, tripping and coupling switch. The grid protection relay is the measuring device within it: it monitors the values and issues the trip command.
When do I need central grid and system protection?
In the low-voltage grid under VDE-AR-N 4105 for generating plants and storage above 30 kVA; below that the integrated protection of the inverters is sufficient. For medium and high voltage, VDE-AR-N 4110 and 4120 apply.
Which quantities does a grid protection relay monitor?
Voltage (over- and undervoltage), frequency (over- and underfrequency), the rate of change of frequency ROCOF or vector shift and the phase sequence – on the CEL-NA-S within 0–560 V, 40–65 Hz, ROCOF 100–2,000 mHz/s, phase shift 1–15°.
Does the relay replace the coupling switch?
No. The relay measures and decides; disconnection is done by the coupling switch, for example a contactor or circuit breaker, which the CEL-NA-S controls via three potential-free changeover relays and whose feedback it checks via a digital input.
Who defines the settings?
The grid operator on the basis of the applicable VDE rule. The relay is installed and parameterised by a qualified electrician; the CEL-NA-S stores up to 64 parameter sets and has an integrated test function.