Grid and system protection (NA protection)
Sale up to −69 %from €199.00 instead of €619.88incl. VATAll sale items →
Grid and system protection (NA protection) disconnects a generating plant from the grid via the coupling switch when voltage or frequency leave the set limits. The CEL-NA-S monitors voltage, frequency, ROCOF/vector shift and phase sequence – for PV, CHP, storage, wind and hydro power.
Protection to VDE-AR-N 4105 and 4110
The German technical connection rules VDE-AR-N 4105 (low voltage) and VDE-AR-N 4110 (medium voltage) define how generating plants and storage are disconnected from the grid in impermissible grid conditions. The CEL-NA-S is a grid and system protection relay to VDE-AR-N 4105/4110/4120 for compliant monitoring.
Functions of the CEL-NA-S
Three potential-free changeover relays control the coupling switch; digital inputs take feedback signals and remote shutdown; Modbus RTU is optional. The internally redundant design makes it functionally safe. Menu-guided operation, an integrated test function, 64 memory locations. Auxiliary supply 24 V DC or 110–230 V AC, modular installation, 107 mm wide.
Frequently asked questions
What is the measuring range of the CEL-NA-S?
Measuring input 3×400 V AC (L1-L2-L3-N), phase-to-phase voltage 0–560 V, phase-to-neutral voltage 0–325 V, frequency 40–65 Hz, ROCOF 100–2,000 mHz/s, phase shift 1–15°.
What is NA protection?
NA protection (Netz- und Anlagenschutz) is grid and system protection. It monitors voltage and frequency at the grid connection of a generating plant and disconnects it via the coupling switch if limits are violated.
Which plants is the CEL-NA-S suitable for?
PV systems, CHP, storage, wind and hydro power plants.
Which auxiliary supply does it need?
24 V DC or 110–230 V AC.
What is a grid and system protection relay?
The measuring device in grid and system protection: it monitors voltage and frequency at the grid connection and trips the coupling switch when a limit is violated. The CEL-NA-S is such a relay for modular installation, 107 mm wide, menu-guided and with an integrated test function.
When does VDE-AR-N 4105 require a central protection relay?
VDE-AR-N 4105 applies to generating plants and storage on the low-voltage grid. Up to 30 kVA the protection integrated in the inverter is sufficient; above 30 kVA the rule requires a central grid and system protection at the point of connection, as formed by the CEL-NA-S with a coupling switch. The settings are specified by the grid operator.
Which protection relay for PV, CHP and storage?
The CEL-NA-S to VDE-AR-N 4105 (low voltage), 4110 (medium voltage) and 4120 (high voltage) monitors voltage, frequency, ROCOF/vector shift and phase sequence and suits PV, CHP, battery storage, wind and hydro power.