Calibrated current transformers for billing
Calibrated current transformers – “conformity-assessed instrument transformers” in German legal metrology – are approved for billing purposes. The type of the plug-on CTs ALO-E and the wound primary CTs WALO-E has been examined by the Physikalisch-Technische Bundesanstalt (PTB); every transformer carries the number of the type-examination certificate and the metrology marking on its rating plate. The legal basis is the German Measures and Verification Act (MessEG) with its ordinance (MessEV) – not the MID, which applies to energy meters.
Not sure which transformer fits?
The assistant asks step by step about purpose, mounting and current and shows the matching articles.
Basics, types, accuracy classes and selection help are on the main page Current transformers.
Products
Versions
ALO-E for primary currents from 50 A to 5000 A, secondary 1 A or 5 A, in accuracy classes 0.2S, 0.2, 0.5S and 0.5. The WALO-E covers 1 A to 40 A in class 0.5. They are 30 mm deep; mounting material for busbar or cable is included, DIN-rail snap-on fixings are available as accessories.
The rotatable, sealable secondary terminal cover short-circuits the transformer when opened. This saves the CT test terminal and allows simpler wiring with lower power loss. After installation, terminal cover and rating plate are sealed, as the instruction manual for conformity-assessed transformers requires.
On request CELSA supplies a test report with error table (ratio error and phase displacement of the individual measurement) for every calibrated transformer.
“MID current transformer”: what is behind the term?
The European Measuring Instruments Directive (MID, 2014/32/EU) covers electricity meters in Annex MI-003. Instrument transformers are not included; in Germany they fall under national legal metrology: conformity assessment under MessEG/MessEV based on a PTB type-examination certificate. “Calibrated current transformer” is the common name – there is no such thing as an “MID current transformer”.
For billing via a CT-operated meter both belong together: the MID energy meter for CT connection and the calibrated, conformity-assessed current transformer. The guide on calibration and MID for current transformers explains the details.
Calibrated CTs and MID energy meters
For CT-operated billing, calibrated current transformers are combined with an MID energy meter for CT connection such as the DMC6 MID or ECM6 MID. The MID marking applies to the meter; the current transformer has its own conformity assessment. Which current transformers match meters is shown by ratio.
Uncalibrated plug-on CTs for operational metering and energy monitoring are listed under plug-on current transformers; split-core CTs are not available calibrated.
Frequently asked questions
What is a calibrated current transformer?
A conformity-assessed current transformer under MessEG/MessEV: its type has been examined by the PTB (type-examination certificate), each unit carries the certificate number and the metrology marking. It is approved for billing, i.e. measurements on which energy invoices are based.
Are there MID current transformers?
No. The MID covers electricity meters (Annex MI-003), not instrument transformers. Current transformers for billing are conformity-assessed nationally under MessEG/MessEV with a PTB type-examination certificate. If you search for “MID current transformer”, you need calibrated CTs such as ALO-E or WALO-E together with an MID meter.
Which accuracy classes are available?
ALO-E in 0.2S, 0.2, 0.5S and 0.5, WALO-E in 0.5. Classes with “S” keep their accuracy down to lower currents than classes without “S”.
Calibrated or MID – what is the difference for current transformers?
“Calibrated” is the correct term for current transformers: conformity assessment under MessEG/MessEV with a PTB type-examination certificate. “MID” is the directive for the meter. Anyone saying “MID current transformer” means, in practice, calibrated CTs for the MID CT-operated meter – exactly the ALO-E and WALO-E.
Do I need calibrated CTs for the MID meter?
Yes, as soon as the measurement is used for billing: the CT-operated MID meter needs calibrated current transformers, the transformer is part of the approved measuring chain. For pure energy monitoring, uncalibrated CTs are sufficient.
Which primary currents are available calibrated?
ALO-E from 50 A to 5000 A and WALO-E from 1 A to 40 A, secondary 1 A or 5 A.
Are there calibrated split-core CTs?
No. CELSA manufactures calibrated transformers as plug-on CTs ALO-E and wound primary CTs WALO-E; the conductor must be free for installation. Split-core CTs are operational metering transformers.
Do I get a test report?
Yes, on request a test report with error table for the conformity-assessed transformer – please state it with your order.
Is the calibration valid in Austria or Switzerland?
The ALO-E and WALO-E are conformity-assessed under German legal metrology (MessEG/MessEV) with a PTB type-examination certificate. Whether the metering point operator or the verification authority in Austria or Switzerland accepts this for billing must be clarified there; we deliver to Austria and Switzerland and provide test report and documents.