Check short-circuit withstand

Will the transformer withstand the fault current of your installation? Converts the rated short-time current to your clearing time.

Input values

Result

Permissible current for this duration
60 kA
Rated dynamic current Idyn (peak)
150 kA

The transformer withstands this short-circuit current.

Heating follows I²·t, therefore I(t) = Ith · √(1 s / t). To IEC 61869-2, Idyn is 2.5 times Ith.

Permissible short-circuit current versus duration: Ith 10 kA at 1 s, 20 kA at 0.25 s; dynamic current Idyn = 2.5 · Ith = 25 kA
Ith applies for 1 s. Because heating grows with I²·t, the transformer tolerates more current for a shorter clearing time: I(t) = Ith · √(1 s / t). The first current peak is covered by Idyn = 2.5 · Ith.