Protection current transformers

Protection current transformers transfer even high fault currents to protection relays and switchgear. CELSA offers ten series from 75 A to 4000 A, secondary 1 A or 5 A, in protection classes 5P5, 5P10, 10P5 and 10P10.

Not sure which transformer fits?

The assistant asks step by step about purpose, mounting and current and shows the matching articles.

Start the transformer finder

Basics, types, accuracy classes and selection help are on the main page Current transformers.

Protection or measuring transformer?

Measuring transformers should saturate quickly above their operating range – expressed by the instrument security factor FS – so that the secondary current does not rise in a fault and connected meters are protected. Protection transformers must do the opposite: saturate as late as possible so that the relay sees the short-circuit current correctly.

5P10 means a composite error of at most 5 % up to 10 times rated current; 10P5 means at most 10 % up to 5 times. All versions have sealable clear polycarbonate terminal covers and double secondary terminals for short-circuiting the winding before the secondary circuit is opened.

Frequently asked questions

What is a protection current transformer?

A current transformer that does not saturate even at short-circuit currents and transfers the current to protection relays and switchgear.

What does 5P10 mean?

A composite error of at most 5 % up to 10 times rated current.

Which primary currents are available?

From 75 A (IB-50) to 4000 A (IRM), secondary 1 A or 5 A.