Protection current transformer 1500/1 A
Protection current transformer for protection relays · ratio 1500:1
8 CELSA protection current transformers with a ratio of 1500/1 A: Protective current transformer (IBR-1, ICM, IER-1 …). Accuracy class 5P5–10P10, rated burden 3.75–15 VA, window for round conductors Ø 30–80 mm. From €101.22 incl. VAT, with datasheet, direct from the manufacturer.
8 products
Products
Frequently asked questions
What does 5P10 mean?
Protection CTs transmit even high overcurrents faithfully so that protection relays trip reliably. In 5P10, "5P" means a composite error of at most 5 %, "10" is the accuracy limit factor: the limit holds up to 10 times the rated current. Available here for 1500/1 A: 5P5, 5P10, 10P5 and 10P10. Protection CTs explained →
What does 1500/1 A mean?
With 1500 A in the primary conductor, the transformer delivers 1 A to the meter or measuring device – a ratio of 1500:1. Meters and instruments are set to this CT ratio. The 1 A secondary keeps cable losses low on long measuring lines.
Will it fit my cable?
The window decides: the types listed here take round conductors of Ø 30–80 mm, depending on the type. The datasheet of each type gives the exact window and busbar dimensions. CT finder →