Calculating a current transformer: ratio, CT factor and sizing

The ratio of a current transformer is the quotient of rated primary and secondary current: Kn = Ipn / Isn. A 400/5 A transformer has a ratio of 80, a 400/1 A transformer 400. Everything else follows: the secondary current is the primary current divided by Kn, the primary current is the measured secondary current times Kn. With 320 A through a 400/5 A CT, it delivers 320 / 80 = 4 A to the instrument.

On an energy meter Kn is called the CT factor or multiplier. A CT-operated meter only counts what flows through the secondary side; consumption is the difference of the readings times the CT factor. Example: three 400/5 A CTs, reading from 1,250.0 to 1,312.5 kWh – that is 62.5 kWh × 80 = 5,000 kWh. Meters with a programmable ratio already display the primary value.

Choose the rated primary current just above the highest operating current. A transformer that is far too large works mostly at part load, where the error limits are wider (class 0.5: ±0.75 % at 20 %, ±1.5 % at 5 % of rated current). For strongly varying loads the S classes 0.5S or 0.2S, defined down to 1 % of rated current, help.

With plug-on CTs the ratio can be reduced by passing the conductor through several times: with n passes Ipn / n applies. A 100/5 A CT with two turns works like a 50/5 A CT. For permanently small currents a wound primary CT is the better choice. The burden in VA is calculated with the VA calculator.

Ratio and CT factor

Current transformerCT factor KnSecondary current at half loadPrimary current at 1 A secondary
[100/5 A](/stromwandler/100-5a)202.5 A20 A
[400/5 A](/stromwandler/400-5a)802.5 A80 A
[1000/5 A](/stromwandler/1000-5a)2002.5 A200 A
[400/1 A](/stromwandler/400-1a)4000.5 A400 A

Kn = rated primary current / rated secondary current. Primary current = secondary current × Kn, energy = difference of readings × Kn.

Calculators and related pages

Recommended Products

FAQ

How do I calculate the ratio of a current transformer?

Rated primary current divided by rated secondary current: 400/5 A gives 80, 150/5 A gives 30, 400/1 A gives 400.

How do I calculate the secondary current?

Primary current divided by the ratio. 250 A on a 400/5 A CT gives 250 / 80 = 3.125 A.

What is the CT factor on an electricity meter?

The ratio of the CTs the meter is connected to. Actual consumption is the difference of the readings times the CT factor, unless the ratio is programmed into the meter.

Can I change the ratio with several turns?

With plug-on CTs yes: if the conductor passes n times through the window, the rated primary current divided by n applies.