Cable cross-section for the burden

Which cross-section does the measuring cable need so that the rated burden is sufficient? The counterpart to the VA calculator.

Input values

Result

Available for the cable
4,4 VA
Calculated cross-section
3,98 mm²
Recommended cross-section
4 mm²
Burden with this cross-section
4,97 VA

Calculated with ρ = 0.0175 Ω·mm²/m (copper), forward and return conductor, plus 0.1 VA for terminal and contact resistance.

1,5 mm² · 2,5 mm² · 4 mm² · 6 mm² · 10 mm² · 16 mm²