Cable cross-section for the burden
Which cross-section does the measuring cable need so that the rated burden is sufficient? The counterpart to the VA calculator.
Input values
Result
- Available for the cable
- 4,4 VA
- Calculated cross-section
- 3,98 mm²
- Recommended cross-section
- 4 mm²
- Burden with this cross-section
- 4,97 VA
Calculated with ρ = 0.0175 Ω·mm²/m (copper), forward and return conductor, plus 0.1 VA for terminal and contact resistance.
1,5 mm² · 2,5 mm² · 4 mm² · 6 mm² · 10 mm² · 16 mm²