Shunt resistor: measuring DC current with 60 mV to 300 mV

A shunt resistor is a low-ohm precision resistor in the DC circuit. When rated current flows through it, a small, precisely defined voltage drops across it – at CELSA 60 mV, 80 mV, 100 mV, 150 mV or 300 mV. A moving-coil instrument or a digital meter measures this voltage and displays it as current. Current transformers only work with AC; for DC the shunt is the classic way.

CELSA manufactures shunts in class 0.5 in three designs: form A for 1 A to 250 A with 60 mV, 100 mV, 150 mV or 300 mV, form B for 250 A to 1000 A (60 mV, 80 mV, 150 mV) and form C for 4000 A at 60 mV. The rated voltage must match the meter input – the analogue ammeters PQ and PAQ and the digital displays with shunt input take 60 mV and 150 mV.

Shunt 500 A / 60 mV in series in a DC circuit with 250 A, 30 mV at the sense terminals, meter shows 250 A
How a shunt measures high DC currents: the current flows through a precisely defined small resistance, and the voltage at the sense terminals is proportional to the current – with a 500 A / 60 mV shunt, 250 A gives exactly 30 mV.

CELSA shunts at a glance

DesignRated currentsRated voltageClass
Form A1 A to 250 A60 mV, 100 mV, 150 mV, 300 mV0.5
Form B250 A to 1000 A60 mV, 80 mV, 150 mV0.5
Form C4000 A60 mV0.5

Intermediate values and special voltages on request. The version is part of the article name, e.g. “Shunt 100A/60mV Kl. 0,5”.

Calculators and related pages

Typical Applications

Recommended Products

FAQ

What does 60 mV mean for a shunt?

At rated current 60 mV drop across the shunt. The resistance is voltage divided by current: a 100 A/60 mV shunt has 0.6 mΩ. The meter needs the matching input – 60 mV is the most common value.

How is a shunt connected?

The shunt is in series with the load circuit, usually in the negative leg. The measuring leads to the meter start at the small voltage terminals, not at the current terminals – otherwise contact resistances falsify the reading.

Does the length of the measuring lead matter?

With moving-coil instruments yes: the lead is part of the measuring circuit and its resistance reduces the reading. Analogue ammeters are therefore adjusted to a defined lead resistance; digital displays with high-impedance input are insensitive.

Which meter fits the shunt?

Analogue: the moving-coil ammeters PQ and PAQ. Digital: the panel meters with shunt input (M1.48, M1.72, M1.96 SR2 for 60 mV and 150 mV; M2.96, M3.48, M3.96.2 SR4 with options such as analogue output and setpoints).

Can I use a current transformer for DC?

No. A current transformer only transfers AC; with DC the core saturates and no secondary signal results. For DC use a shunt with a matching display.