Analogue panel meters: moving-iron, moving-coil or bimetal?
Analogue meters show current and voltage with a pointer on a scale – without auxiliary supply, without configuration and still readable during disturbances. In panels, cabinets and distribution boards they therefore remain the standard indication for a glance at the load. Which instrument fits is decided by the movement: it determines whether AC or DC quantities are measured and what the pointer shows.
CELSA manufactures analogue panel meters with bezels of 48, 72 and 96 mm: the moving-iron ammeter EQ and voltmeter EQ for AC quantities, the moving-coil instruments PQ (90° scale) and PAQ (240° scale) for DC quantities, and the bimetal ammeters BIQ and BOQ with a red maximum pointer. AC ammeters are connected directly or via a current transformer with 1 A or 5 A, DC instruments via a shunt with 60 mV.
Which movement for what?
| Movement | CELSA types | Quantity | Indicates | Feature |
|---|---|---|---|---|
| Moving-iron | EQ ammeter, EQ voltmeter, EQn-SWT | AC current, AC voltage, 15 to 400 Hz | RMS value (also with harmonics) | polarity-independent, overload-proof to DIN 43780; EQn-SWT with selector switch for three phases, class 1.5 |
| Moving-coil | PQ (90°), PAQ (240°) | DC current, DC voltage | arithmetic mean | class 1.5, low consumption; overload-proof 1.2 × IN continuous, 10 × IN for 5 s; connection via 60 mV shunt |
| Bimetal | BIQ | AC current (thermal) | mean RMS value, slow; red maximum pointer holds the peak | ignores short current peaks – thermal load of cables and transformers; –10 to +55 °C; sealable reset button |
| Bimetal + moving-iron | BOQ | AC current via CT 1 A or 5 A | black pointer instantaneous value, red maximum pointer thermal maximum | two movements in one housing, temperature-compensated |
All types with bezels of 48, 72 and 96 mm; scales to CT ratio (e.g. 250/5 A) or direct range.
Calculators and related pages
Typical Applications
- Switchboards and low-voltage main distributions
- Thermal monitoring of cables and transformers (BIQ, BOQ)
- DC systems, batteries and rectifiers (PQ, PAQ with shunt)
Recommended Products
FAQ
Moving-iron or moving-coil – which movement do I need?
Moving-iron for AC current and voltage (EQ), moving-coil for DC current and voltage (PQ, PAQ). A moving-coil instrument shows nothing useful on AC, a moving-iron instrument measures DC only inaccurately.
How do I connect an analogue ammeter?
AC ammeters directly up to the direct range, above that via a current transformer with 1 A or 5 A secondary – the scale is then labelled with the ratio, e.g. 250/5 A. DC ammeters measure the voltage drop across a shunt, usually 60 mV.
What does the maximum pointer of a bimetal ammeter do?
The red maximum pointer is pushed along by the measuring pointer and stays at the highest value reached. This shows how heavily a cable or transformer has been thermally loaded since the last reset. It is reset with the sealable button.
Which accuracy class do analogue panel meters have?
The moving-coil instruments PQ and PAQ and the moving-iron selector ammeter EQn-SWT are class 1.5. The class states the permissible error as a percentage of full scale.
Which sizes are available?
Bezels of 48, 72 and 96 mm, the usual grid for panel cut-outs. Exact mounting dimensions are in each datasheet.
Analogue or digital?
Analogue when the trend at a glance, robustness and operation without auxiliary supply matter. Digital when limit values, analogue outputs or interfaces are needed – that is what the digital panel meters of the M series are for.