Summation current transformers: several feeders on one meter
A summation current transformer adds the secondary currents of several main current transformers (x/5 A or x/1 A) into a single output signal of 5 A or 1 A. One measuring device or energy meter then records the total current and energy of several feeders, incomers or transformers.
CELSA makes two series: the SSR summation current transformers for plug-on CTs and the SSRK-2 to SSRK-6 for split-core CTs. The SSRK sum 2 to 6 currents in the secondary circuit of low-power current transformers; with accuracy class 0.5 and a burden of only 0.2 VA they are matched to the small output power of split-core CTs.
Typical Applications
- Total consumption of several feeders with one energy meter
- Sum of several incomers or transformers
- Retrofit with split-core CTs and SSRK
Recommended Products
FAQ
What is a summation current transformer used for?
It combines the secondary currents of several current transformers into one signal. A single measuring device or energy meter then records the total consumption of several feeders instead of one device per feeder.
What do the main current transformers need?
All main CTs need the same ratio and the same secondary current (1 A or 5 A) – or the summation CT is matched to the different ratios. All CTs must also be connected with correct polarity (P1/P2 primary, S1/S2 secondary), otherwise currents cancel out instead of adding up.
Which ratio do I set on the meter?
The sum of the rated primary currents to the output current of the summation CT. Example: three main CTs 400/5 A on an SSR 5+5+5/5 A give 1200/5 A.
What is the difference between SSR and SSRK?
The SSR are designed for plug-on current transformers. The SSRK-2 to SSRK-6 are designed for split-core current transformers: they sum 2 to 6 currents of low-power CTs, have accuracy class 0.5 and a burden of only 0.2 VA.