Which accuracy class do I need?

Permissible current error and phase displacement of the classes to IEC 61869-2 – including partial load, where the differences are largest.

Input values

Limits of the class 0,5

5 %± 1,5 %± 90′
20 %± 0,75 %± 45′
100 %± 0,5 %± 30′
120 %± 0,5 %± 30′

Permissible error to IEC 61869-2

Applicable reference point
100 %
Current error
± 0,5 %
Phase displacement
± 30′
Equals at the secondary output
± 25 mA

The standard only specifies limits at the listed reference points. Between two points the value of the next lower one applies. The values apply at rated burden and rated frequency.

Error limits of accuracy classes 0.2S, 0.5, 1 and 3 to IEC 61869-2 across the operating current from 1 to 120 % of rated current
In the rated range the value that gives the class its name applies; at partial load the limits widen. Billing requires class 0.5 or better.