Rogowski coil: function, advantages and use of flexible current measurement
A Rogowski coil is a flexible air-core coil without an iron core that is placed around the conductor and closed with a clasp. The alternating current in the conductor induces a voltage in the coil proportional to the rate of change of the current. A downstream integrator – in an instrument or energy meter with Rogowski input – turns it into a signal proportional to the current.
Because there is no iron core, the coil cannot saturate: it measures small and very large currents with the same coil. The CELSA RALO Rogowski coils deliver 100 mV/kA at 50 Hz and measure up to 100 kA in the frequency range from 40 Hz to 20 kHz – at 1000 A that is 100 mV.
RALO is available with coil windows of 95, 140 and 190 mm (D95, D140, D190) and leads of 3, 5 or 10 m. They comply with IEC 61869-10 and IEC 61010-2-030, are rated for 1000 V CAT III or 600 V CAT IV and have IP 54 protection.
Rogowski coil or current transformer?
| Rogowski coil RALO | Current transformer (e.g. ALO) | |
|---|---|---|
| Core | air coil, flexible, no iron | iron core, rigid |
| Output | 100 mV/kA at 50 Hz, integrator required | 1 A, 5 A or 333 mV, directly to instrument or meter |
| Measuring range | up to 100 kA with the same coil | according to rated primary current, e.g. 400/5 A |
| Saturation | none | from the instrument security factor (e.g. FS 5) |
| Frequency | 40 Hz to 20 kHz | mains frequency (50 Hz) |
| Installation | place around cable or busbar, no shutdown | plug-on CT: conductor through the window |
| Accuracy | linearity ±0.2 % of reading, position error max. ±0.5 % | class 0.2S to 3 to IEC 61869-2 |
| For billing | no | yes, as calibrated CT (ALO-E) |
Calculators and related pages
Typical Applications
- Current measurement on thick cable bundles and wide busbars
- Very high currents up to 100 kA without saturation
- Retrofitting energy monitoring and power analysis without shutdown
Recommended Products
FAQ
What is a Rogowski coil?
A flexible air-core coil placed around a conductor that measures the alternating current via the induced voltage – without an iron core and without galvanic connection to the conductor.
What advantages does a Rogowski coil have over a current transformer?
It is light and flexible, does not saturate and measures up to 100 kA with the same coil. It is placed around the conductor without opening the circuit – also on thick cable bundles or wide busbars.
Why does a Rogowski coil need an integrator?
The coil delivers a voltage that follows the rate of change of the current, not the current itself. Only the integrator in the instrument or meter turns this into a signal proportional to the current. A Rogowski coil is therefore only connected to devices with a Rogowski input, not to 1 A or 5 A inputs.
How large is the output signal of the RALO?
100 mV per 1000 A at 50 Hz. 500 A give 50 mV, 10,000 A give 1 V. Because the induced voltage rises with frequency, the raw signal is larger by a factor of 1.2 at 60 Hz; the integrator compensates for this.
Can a Rogowski coil measure direct current?
No. A constant current does not change and induces no voltage. Shunts are suitable for direct current.
How accurate is a Rogowski coil?
With the RALO the linearity error is at most ±0.2 % of reading, the ratio error less than 0.2 % with the conductor centred at the clasp (25 °C). If the conductor is not centred, a position error of at most ±0.5 % is added.
May I use a Rogowski coil for billing?
The RALO is not calibrated. Billing third parties requires calibrated current transformers such as the ALO-E together with an MID meter.