Homepage About us News Contact Service Products Downloads 🇩🇪 Deutsch 🇬🇧 English 🇪🇸 Español

ECM80-M MID

Request now
Data sheet Instruction manual M-Bus Config
CELSA ECM80-M MID
Basic data
Item number
70143-1211

80A three-phase energy meter with built-in communication

  • Certified MID version
  • For M-Bus communication
  • Direct connection up to 80 A
  • Fully bidirectional four-quadrant metering for all energies and powers
  • For 3 / 4-wire networks with balanced or unbalanced load
  • Class B according to EN 50470-3
  • S0 output for energy pulse output
Technical data
Auxiliary voltage
of measuring circuit Un ± 20%
Consumption
7.5 VA, 0.5 W
Ambient conditions
Operation -25 - 55 °C
Storage -25 - 75 °C
Humidity 0 - 80 RH
Montage
DIN-Schienen Montage
Electrical connection
Display
Type
LCD
Number of digits
8
IP protection class
IP51
Connections
IP protection class
IP20
Measurement inputs conductor cross-section
1.5-35 mm²
Tariff outputs conductor cross-section
0.14-2.5 mm²
Tariff input
Tariff input
Yes
Voltage range tariff 2
80 - 276 AC-DC
Metrological LED
Pulse valence
1000 imp./kWh
Pulse duration
10 ± 2 ms
Communication
Normative standards
EN1434-3
Interfaces
M-Bus
Protocols
M-Bus
Load unit
1
speed
300 - 38400
Measurement
Active energy accuracy
Class B according to EN 50470-3
Reactive energy accuracy
Class 2 according to IEC/EN 62053-23
Starting current
20 mA
Minimum current
250 mA
Transition current
500 mA
Rated current
0 - 80 A
Nominal current
5 A
Frequency
50 - 60 Hz
S0 output
Number of S0 outputs
1
Maximum current
27
Maximum voltage
27 DC
Pulse output
100 Imp./kWh
Pulse duration on
50 ± 2 ms
Pulse duration off
30 ± 2 ms