WECM80-E MID

| Basic data | |
|---|---|
Item number | 70143-1113 |
Single-phase 80A energy meter with built-in communication
- Certified MID version
- For Ethernet (Modbus TCP) communication
- Direct connection up to 80 A
- Fully bi-directional 4-quadrant measurements for all energies and powers
- Class B according to EN 50470-3 (MID)
- 8 MB for data logging and automatic/manual data transfer
- S0 output for energy pulse output
- LCD display with 7 main digits
| Technical data | |
|---|---|
Auxiliary voltage | of measuring circuit Un ± 20% |
Consumption | 7.5 VA, 0.5 W |
Ambient conditions | Operation -25 - 55 °C Storage -25 - 75 °C Humidity 0 - 80 RH |
Montage | DIN-Schienen Montage |
Electrical connection | |
Display | |
Type | LCD |
Number of digits | 7 |
IP protection class | IP51 |
Connections | |
IP protection class | IP20 |
Measurement inputs conductor cross-section | 1.5-6 mm² |
Tariff input | |
Tariff input | No |
Metrological LED | |
Pulse valence | 1000 imp./kWh |
Pulse duration | 10 ± 2 ms |
| Communication | |
|---|---|
Normative standards | IEEE802.3 |
Interfaces | Ethernet (10/100 Base T) |
Protocols | Modbus TCP/IP, HTTP, NTP, DHCP |
speed | 10/100 Mbps |
Webserver 8MB Data storage | |
| Measurement | |
|---|---|
Active energy accuracy | Class B according to EN 50470-3 |
Reactive energy accuracy | Class 2 according to IEC/EN 62053-23 |
Starting current | 20 mA |
Minimum current | 250 mA |
Transition current | 500 mA |
Rated current | 0 - 80 A |
Nominal current | 5 A |
Frequency | 50 - 60 Hz |