IAG

IAG

Current transformer

Request nowDatasheet (PDF)

Article features

  • Transformer core can be easily divided
  • excellent for retrofitting, as the primary circuit does not have to be interrupted
  • simple and secure attachment to busbar - audible latching of current transformer
  • well fixable by some clamping screws
Round conductor
Ø 80 mm
Primary rail
30 x 15 mm, 80 x 12 mm, 120 x 10 mm, 4 x 120 x 10 mm
Dimensions (W × H × D)
163 × 200 × 41 mm
Rated current
600, 750, 800, 1000, 1200, 1500, 1600, 2000, 2500, 3000, 4000, 500 A
Instrument security factor
FS 5
Round conductorØ 80 mm
Primary rail30 x 15 mm, 80 x 12 mm, 120 x 10 mm, 4 x 120 x 10 mm
Dimensions (W × H × D)163 × 200 × 41 mm
Rated current600, 750, 800, 1000, 1200, 1500, 1600, 2000, 2500, 3000, 4000, 500 A
Instrument security factorFS 5

Conditions of use

Secondary current5 A oder 1 A
Nominal frequency50 - 60 Hz
max. permissible operating voltage720 V
Test voltage3 kV / 1 min
Thermal rated continuous currentIcth = 1,2 x Ipr
Thermal rated short-time withstand currentIth = 60 x Ipr
Rated impulse currentIdyn = 2,5 x Ith
Overcurrent rating (FS)n < 5
Insulation classE / F / H
Normative standardsIEC 61869 Teil 1 + 2 / DIN EN 42600
HousingGehäuse aus selbstverlöschendem PA66 V0 nach UL 94

Environmental conditions

Installation locationIndoor use
Ambient temperature (operation)-40°C ... +60°C
Ambient temperature (storage / transport)-40°C ... +60°C
Altitudeup to 1000 m