Homepage About us News Contact Service Products Downloads 🇩🇪 Deutsch 🇬🇧 English 🇪🇸 Español

SSRK-2

for cable-mounted current transformers

Request now
CELSA SSRK-2
Basic data
Item number
70140-7001
Weight
400

The SSRK-2 to SSRK-6 current summing transformers are specifically designed for use with split-core current transformers (CTs). They enable the summing of 2 to 6 currents in the secondary circuit of low-power current transformers. Their compact design and high accuracy (Class 0.5) make these transformers ideal for energy measurement in low-voltage networks. The low burden of just 0.2 VA is specifically tailored to the low output power of split-core current transformers.




Data Downloads
Technical data
Supply
Supply voltage
24 V DC / 110-230 V AC (48-63 Hz)
Measuring circuit
Measuring input
3x400 V AC (L1/L2/L3/N)
Inputs/outputs
Output relays
3x changeover contacts
Relay rated current
5 A / 250 V AC
Digital inputs
I1-I3; optional I4-I5
Communication
Interface
Modbus RTU (RS-485), optional
Mounting & connection
Mounting
DIN rail EN 60715
Conductor cross-section
max. 2.5 mm², stripping length 8 mm
Tightening torque
max. 0.5 Nm
Protection classes
Housing
IP2X/B
Terminals
IP2X/B
Environmental conditions
Operation
-25 ... +65 °C
Storage
-40 ... +70 °C
Humidity
5 ... 95 % RH, non-condensing
Standards
Supported standards
VDE-AR-N 4105/4110
EN 50549-1/-2
CEI 0-21
C10/11
Data sheet