Current transformer 10/1 A
Ratio 10:1 · primary current 10 A, secondary current 1 A
2 CELSA current transformers with a ratio of 10/1 A: Plug-on / winding current transformers (WALO) and Calibrated clip-on current transformers (WALO-E). Accuracy class 0.5 or 1, rated burden 1.5–5 VA. From €103.48 incl. VAT, with datasheet, direct from the manufacturer.
Frequently asked questions
What does 10/1 A mean?
With 10 A flowing in the primary conductor, the transformer delivers 1 A to the meter or measuring device – a ratio of 10:1. Meters and instruments are set to this CT ratio. The 1 A secondary keeps cable losses low on long measuring lines.
How much burden (VA) do I need?
The rated burden must cover the consumption of the connected devices plus the losses of the measuring line, without being much higher. The types listed here offer 1.5–5 VA. The VA calculator determines the value. VA calculator →
Which accuracy class?
For 10/1 A the classes 0.5 and 1 are available here. Billing-relevant metering requires class 0.5 or better; for display and monitoring class 1 is usually sufficient. Accuracy class comparison →