Current transformers

All CELSA current transformers in one list: plug-on CTs for new installations, split-core CTs for retrofits without disconnecting, calibrated CTs for billing, protection CTs for protection relays and summation CTs for several feeders. Made in Römerberg, Germany, to DIN EN 61869.

Not sure which transformer fits?

The assistant asks step by step about purpose, mounting and current and shows the matching articles.

Start the transformer finder

Basics, types and selection criteria are explained in the current transformer guide →

Sub-groups

Products

Which current transformer fits?

TypeApplicationPrimary currentSecondaryClasses
Plug-on CT ALOnew installation, switchgear, main distributionup to 6000 A1 A, 5 A, 333 mV0.5 – 3
Wound primary CT WALOsmall currents with own primary winding1 A – 40 A1 A, 5 A, 333 mV0.5, 1
Split-core CTsretrofit without disconnecting, cable and busbar60 A – 3000 A1 A, 5 A, 333 mV0.5, 1, 3
Calibrated CTsbilling to third parties1 A – 5000 A1 A, 5 A0.2S – 0.5
Protection CTsprotection relays, overcurrent protection75 A – 4000 A1 A, 5 A5P5 – 10P10
Summation CTsseveral feeders on one meter2 – 9 inputs1 A, 5 A0.5, 1

The filters of the list narrow down ratio (e.g. 400/5 A) and window; every ratio has its own overview, such as current transformer 400/5 A.

Choosing a current transformer

Four values decide: the rated primary current (slightly above the highest operating current), the secondary current of the instrument (5 A, or 1 A for long measuring leads), the accuracy class (0.5 or better for billing, otherwise usually 1) and the burden in VA needed by instrument and lead together. The guide choosing a current transformer explains it step by step; the VA calculator works out the burden.

The type follows from the installation: if the conductor is free (new installation), the plug-on CT is the common and most economical solution. To retrofit a live installation, a split-core CT is placed around the cable or busbar. A comparison of all types is in current transformer types compared.

Frequently asked questions

What is a current transformer?

A current transformer maps a high primary current in a fixed ratio to a small secondary current – usually 5 A or 1 A – that meters, instruments and protection relays can handle safely. A 400/5 A transformer delivers 5 A to the instrument at 400 A in the conductor.

Which ratio do I need?

Choose the rated primary current just above the highest operating current of the conductor and the secondary current according to the instrument input. Every ratio has its own overview, e.g. current transformer 400/5 A or 100/5 A.

Does the circuit have to be interrupted for installation?

For a plug-on CT yes, because the conductor is passed through the window. Split-core CTs are opened and placed around the conductor – without interrupting the primary circuit.

Which current transformers are approved for billing?

Billing to third parties requires calibrated (conformity-assessed) current transformers together with a MID meter. CELSA makes the plug-on CTs ALO-E and the wound primary CTs WALO-E with PTB type approval for this.